Additional information
Weight | 1.4 lbs |
---|---|
Dimensions | 4 × 4 × 4 in |
Brand | |
Series | |
Size | |
MPN | 0685681, 0685688 |
Connection | all NPT & SW, Flanged Connection Only |
Steam and pressure controls since 1951
$105.00 – $213.00
Cover Studs & Nuts for TD62,62L,TD62M,TD62LM Thermodynamic Steam Trap, 8 9 8A
Available size: 1/2″, 3/4″, 1″
Available for NPT & SW or Flanged
Limiting Conditions
Body design conditions ANSI 600
– PMA (Max. allowable pressure)
1500 psig / 103 barg
– TMA (Max. allowable temperature)
977°F / 525°C
– Cold hydraulic test pressure
2250 psig / 155 barg
– Minimum operating temperature
-22°F (-30°C)
TD62LM (Low capacity)
Minimum pressure for satisfactory operation is 120 psig, 8 barg. Maximum back pressure should not exceed 50% of the inlet pressure under any conditions of operation, otherwise the trap may not shut.
TD62M (Standard capacity)
Minimum pressure for satisfactory operation is 20 psig, 1.4 barg. Maximum back pressure should not exceed 80% of the inlet pressure under any conditions of operation, otherwise the trap may not shut.
TI-2-525-US
Weight | 1.4 lbs |
---|---|
Dimensions | 4 × 4 × 4 in |
Brand | |
Series | |
Size | |
MPN | 0685681, 0685688 |
Connection | all NPT & SW, Flanged Connection Only |
Reviews
There are no reviews yet.